Facilitates compliance with BS5839-9 when correctly installed.
Mains supply
230V 50/60Hz.
Mains rated current
500mA.
Internal power supply
19V-28.5V (27V nominal). Ripple 7V maximum (battery fault).
Total output current limited to
1.5A @ 230Vac
Quiescent current
100mA (controller with fault buzzer sounding) plus 1mA per Type A outstation and 3.2mA per Type B outstation.
Max battery size and type
2 x 12V 7Ah VRLA connected in series.
No. of lines
4 (expandable to 12 via an ECU-8S 8 line expansion unit).
Auxiliary relays
Changeover fault relay (failsafe). 30V 1A max.
Open collector outputs
(OP1): Activates when the ECU is ringing; (OP2) Activates when there is an active accessible toilet alarm call; (OP3) Closes when the handset is off hook and remains active for 2 mins after it is replaced. 24V, 50mA max.
Other outputs
+24 V. Typically used to supply power to equipment connected to the ECU’s open collector outputs (relays, etc).
Engineer (AL3) functions
Engineer mode and reset buttons (internal).
Indicators
128 x 64 pixel LCD display; Disablement; System fault; PSU fault; General fault; Power on.
2 x CAT5 connectors provided for an optional ECU-8S expansion unit (leads supplied with ECU-8S). ECU721 network card allows the connection of up to 3 additional ECU-4/8 controllers (1 x ECU721 per ECU-4/8).
Product dimensions (mm)
410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid). Handset protrudes 80 mm beyond lid.
Construction & finish
Metal lid and base, RAL7035 grey texture.
IP Rating
IP20.
Weight
3.1kg (without batteries).
Operating conditions/temperature
-5ºC to +40ºC. Max relative humidity: 95%.
Reviews
There are no reviews yet.
Be the first to review “SigTEL 4 Line Master Controller” Cancel reply
Reviews
There are no reviews yet.