4 Zone Fire Alarm Panel

Features:
• Operates on 230 V AC, 50 Hz AC supply
• Battery backup with built in charger
• Fire, fault status in unambiguous colored LED indications.
• 16 x 2 line dot matrix LCD display
• Zone wise fire, open, short LED indications.
• External switches to test each zone fire, open, short status manually.
• External switch for reset, Silence, Lamp test.
• Zone isolation facility with loop voltage cutoff.
• Relay O/P for actuators.
• Mains on, System On, Charger on, visual indications.
• Battery Low & Common fire indications
• Auto dialer attachable facility
• Enough inside space for battery
• Attachable with all types of detectors.

Description

TECHNICAL SPECIFICATIONS
Panel Operating Condition Operating Voltage
AC Power 220v AC, 50Hz ± 10%
Standby 24v DC
Operating Temperature 0°C to 40°C
Operating Humidity 95% (non-condensing)
Zone Operating Condition
Normal Loop Voltage 23v DC
Open Threshold Current 4.4 mA
Short Threshold Current 35 mA
Fire Threshold Current 15 – 35 mA
Alarm Outputs Hooter Output 1 A (24v DC) (Normal)
NB Hooter output current can be increased as per customer requirement.
Remote Outputs
Fire Contact1 (C, NO, NC) 240v AC/24v DC@ 5A
Fault Contact (C,NO,NC) 240v AC/24v DC@ 5A