4 loop Addressable Fire Control Panels

Features
DS80AP.03.2014
Analogue Addressable
4 Loops Fire Control Panels
Elite
UL 864 9th Edition listed
Multi-Loop Analog Addressable Loops Field
upgradable to 4
126 primary points per loop
Powerful, network wide cause and effects (500
total). Fully user programmable by point or zone.
800 points per panel when using devices with
sub-points
Up to 10,000 ft. wiring length on SLC loop
64 Panels on a network
Programmable through a PC connection to the
panel, or through keypad
Programmable relays – 5
Supervised Powered Outputs – 3
Programmable Notification Appliance Circuits: 4
Power per NAC: 1.6 Amps Max
Programmable outputs on SLC loop
Programmable Function button on front display
Fire Drill button on front display
Day and night sensitivity settings (user
programmable)
Power Supply: 5.25 Amp, regulated & integrated
LCD Display: 8×40
Zonal Mode: Annunciation by zone w/o individual
relationships
Panel Ring Modes: Common, Zonal, Stage 2
NAC Outputs programmable as Continuous,
March, Temporal
Program Cause and Effects AND, OR, or Any
Two (Cross Zone)
Battery size: Up to 17 Ah in standard enclosure; up to
52 Ah with external cabinet
Access levels: 3
Access key switch: Yes
Recognized for use in High Rise
One man walk test – Fire Test Mode
Available with semi flush trim ring
Available in Red or Grey

Description

Construction
Primary AC
Output DC
Power Supply
Charger Current
Weight
Colour
Display
Zones
SLC loops
Devices per loop
NAC Outputs
Relay Outputs
Voltage Outputs
Aux. Power
Aux. Inputs
1.5mm mild sheet steel
120VAC @ 2 Amps 60hz (Optional 240 VAC 50hz)
24VDC @ 4 Amps
5.25 Amp regulated and integrated
1.25 Amps max.
11kg (without batteries)
Red (optional grey)
8 line x 40 character LCD (320 characters total)
500 Zones per network
2 or 4 (class A or B)
126 sensors & modules (800 addresses + sub-addresses max. per panel)
(4) 1.6 Amp @ 24VDC (class B)
(5) Form C 1 Amp @ 30VDC
(3) 500mA @ 24VDC, reverse polarity supervised
500mA @ 24VDC
(3) digital pull downs

The Elite analog addressable Fire Control Panel supports 2 or 4
SLC loops for a total of 500 primary points or 800 points using
subpoints.
SLC loop communications uses standard twisted pair cabling,
shielded cable is not necessary.
The panel may be configured with various communication cards;
Communications options support central station monitoring,
Virtual Panel, and networking.
The Panel can be configured as a stand alone panel with just
a few devices for a small building, it can also operate as the
building system and can be part of a network with a total of 64
nodes serving a multiple building campus or a very large facility.
Auto Learn capability provides a convenient method to
troubleshoot new installations before final programming is
loaded.