Compatible with C-TEC’s XFP/ZFP CAST Protocol Addressable Fire Panels.
Type
Muti-Sensor.
Application/operation
As well as operating independently, the CA414’s smoke & heat sensors combine to produce a sensitive response to freely burning fires, e.g. when a rise in heat is detected, its smoke response level reduces for improved detection and reduced false alarms.
Application temperature
25°C typical, 50°C max (in Class A1R and Class A2 mode); 40°C typical, 65°C max (in Class B mode). In A1R mode the detector will also trigger if it detects a sudden rise in temperature.
Static response temperature
54°C min, 65°C max (In Class A1R and Class A2 mode); 69°C typical, 85°C max (in Class B mode).
Sensitivity
Option to set 5 different sensitvity levels at the fire panel. See Operation Modes tab below for details.
Supply wiring
2-wire, polarity sensitive.
Supply/operating voltage
27 to 40V DC.
Quiescent current
60µA @ 24V.
Alarm current
6mA (LEDs illuminated).
Indicators
2 LED indicator strips emitting red light when in alarm offering 360º visibility. Optional remote LED.
Connections
Via CA408 base: 1 +Ve IN (analogue swich); 2 +Ve OUT (analogue switch); 3 Remote LED +Ve; 4 0V; 5 0V; 6 Screen; 7 Screen.
Product dimensions (mm)
102.2mm diameter x 37mm deep (detector only); 102.2mm diameter x 57.5mm deep (detector in base).
Construction & finish
White polycarbonate casing rated to UL94 V-2 with nylon parts.
IP Rating
IP42.
Weight
99g (not in base); 154g (in base).
Operating conditions/temperature
-20ºC to +85ºC.
Notes
Requires a CA408 CAST base. CA408R relay base also available.