XFP 1 Loop 32 Zone Addressable Fire Panel

PROTOCOL FEATURES:

‘CAST’ is the world’s most-advanced ‘distributed intelligence’ fire alarm system protocol. Conceived, designed and realised by C-TEC as part of a five-year, multi-million pound project, it involved the creation of a powerful proprietary communication protocol (C-TEC Addressable System Technology, CAST) and multiple control panels & field devices. Key features include:
• 255 devices per loop.
• Autonomous decision-making for faster response times.
• Multiple type codes.
• 40V loop drive voltage.
• Two ‘soft’ addressing options – automatic via the panel or manual via a powerful handheld programmer.
• Powerful multi-level addressing facilitates easy device addition and swapped device identification.
• Multiple functionality at a single address (integrated devices) – due 2019.
• Volumes, tones & detector modes can be changed at compatible panels.
• High-speed data transmission and robust data transfer.
• Intrinsically EN54-13 compliant.
• Provides geographical location of short and open circuit faults (a short circuit isolator is included as standard in every CAST field device).
• Replace device function.
• Programmable multi-function status LED.
• Future seamless integration with other CAST life safety systems reducing energy, servicing, installation and repair costs.
• Designed and manufactured in the UK.

PANEL FEATURES:

• Pending certification to EN54-2/4 by the Loss Prevention Certification Board (LPCB).
• Two independently programmable conventional sounder circuits.
• Two programmable inputs.
• A fault output relay and three programmable relay outputs with voltage free changeover contacts.
• A selection of zone dependency/coincidence functions.
• A day/night (building occupied/unoccupied) function.
• An investigation delay period function.
• Phased evacuation facility.
• An alarm counter that records how many times the panel has been in alarm state.
• Powerful short circuit protected loop drivers.
• An integral EN54-4/A2 switch mode.
• Adjustable contamination levels.
• Earth fault monitoring.
• Combined keypad / keyswitch entry to Access Levels 2 and 3.
• 999 event monitoring.
• An intuitive Windows based upload-download PC program.
• Up to eight XFP main panels (any variant) can be connected onto a two-wire RS485 network. Alternatively, up to eight XFP repeaters can be connected to any non-networked main panel.

Description

Approvals/certifications Certification to EN54-2/4 by the LPCB pending.
Protocol/compatibility C-TEC CAST.
Mains supply 230V 50/60Hz.
Mains rated current 680mA maximum.
Internal power supply 27Vdc nominal.
Total output current limited to 3A @ 230Vac (Imax.A 250mA; Imin. 70mA).
Quiescent current 80mA (loop unloaded).
Max battery size and type 2 x 12V 7Ah VRLA connected in series.
No. of loop drivers 1.
Max. loop output current 500mA (40V max).
Max. loop length 1KM.
Max. addressable devices per loop 255.
No. of conventional sounder circuits 2 (Max. length per circuit is 500m).
EOL resistor value 6800? 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current 400mA.
Auxiliary relays 3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs 24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs 2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
PC connection PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.
Indicators 2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; System Fault.
Connections Fixed, largest acceptable conductor size 1mm2.
Expansion connections 2-wire RS485 network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater network).
Product dimensions (mm) 410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Construction & finish Metal.
IP Rating IP30.
Weight 4.5kg (no batteries).
Operating conditions/temperature -5ºC to +40ºC. Max relative humidity: 95%.